1.Analysis of cause of failure switching-on of the circuit breaker

1Solution for under-voltage coil not operating (normal voltage): change the under-voltage coil

2Solution for failure operation of switching-on coil after pressing the switching-on button: replace the under-voltage coil.

3Solution for poor contact of switching-on button: replace the

4Solution for burnt down of fusible core of control loop: replace the fusible core after confirming that the control loop is normal without short circuit.

5Solution for failure energy storage of circuit breaker: check control power voltage of the motor shall be≥ 85% .

6Control power voltage of the switching-on electromagnet shall be less than 85%. Solution: power voltage of switching-on electromagnet must be≥ 85%.

7 Solution for damage of switching-on electromagnet: replace the switching-on electromagnet.

8Solution for poor contact of secondary loop of the drawing circuit breaker: after removing the drawer circuit breaker, move to the “connecting” position. Check whether the secondary loop is connected reliably.

9 Solution for stop position at the universal changeover switch: rotate the switch to the left power transmission or the right power transmission。

2.Analysis for failure switching-off of main switch of the feeding cable cabinet

 1Solution for poor contact of switching-off button: replace the switching-off button.

 2Solution for burning down of switching-off coil: replace the switching-off coil.

3 Analysis for reverse rotation or failure rotation of main varmeter

1 The capacitance compensation power too high or advanced: adjust the capacitance compensation to 0.92-0.97.

2Solution for incorrect phase sequence of feeding cable of transformer: re-adjust phase sequence.

3Solution for normal current and voltage loop: replace with varmeter.

4. Analysis for failure automatic feeding of capacitance cabinet

1 Solution for failure wiring of current sampling signal wire: wire the current sampling signal wire.

2 Solution for burnt down of fusible core of the control: replace the fusible core.

3 Solution for too high voltage and over-voltage displayed by control: adjust over-voltage protection point.

4Solution for low current and control display in advance: after increasing current, it operates automatically.

5Solution for over-voltage display on the compensation instrument of the capacitance cabinet: set the voltage higher than actual voltage.

6 Solution for failure wiring of current sampling signal wire: wire the current sampling signal wire.

7Solution for burning down of fusible core of compensation control instrument: replace the fusible core.

8Solution for low current: after the current has been increased, further commission and handle.

 

5.Analysis for failure rotation of watt hour meter of the drawer outlet wire

1Solution for checking poor contact of secondary plugs: adjust contact of the secondary plug.

2Solution for normal voltage and current: replace the watt hour meter.

 

6. Analysis for failure automatic feeding of changeover of dual power

1Solution for universal changeover switch switched to the automatic position: rotate the switch to the automatic position.

2Solution for manual changeover switch not rotated to automatic position: rotate the manual and automatic changeover switch to the automatic position.

3Solution for failure closure of over-voltage tripper: check whether the voltage is consistent with that of the tripper V ≥ 85%.

4Solution for failure closure of timely relay: check contacts 2#7# of the time relay are normal or not.

5. Solution for failure resetting of shunt mechanism of circuit breaker: check whether mechanical interlocking is loosened or not, and if there is any blocking.

 

7. Analysis for power factor of the capacitance cabinet not above 0.9

1Solution for lowered capacity of capacitor: replace capacitor.

2 Solution for failure power connection of partial loops: check, handle and replace.